YT102C Conventional Smoke detector
This detector is designed to provide open area protection and to be used with most conventional fire alarm control panel.
- Overview
- Related Products
The device is photoelectric detector uses a state of-the-art optical sensing chamber. This detector is designed to provide open area protection and to be used with most conventional fire alarm control panel.
Two LEDs on each detector provide local 360° visible alarm indication. They flash every 5 seconds indicating that power is applied and the detector is working properly. The LEDs latch on in alarm. LEDs will be off when a trouble condition exists indicating that the detector sensitivity is outside the listed limit. The alarm can be reset only by a momentary power interruption.
SPECIFICATIONS
Operating Voltage Range: 9 to 28 VDC Volts Non-polarized
Standby Current: ≤60µA@24VDC
Maximum Alarm Current (LED on): ≤30mA@24VDC (1K Ohm current-limiting resistance)
Operating Humidity Range: ≤95%RH(40°C±2°C) Relative Humidity, Non-condensing
Operating Temperature Range: -10°C to 50°C (14°F to 122°F)
Smoke Alarm Sensitivity: 0.15-0.3dB/m
Temperature Sensitivity: 57°C (135°F) A1R (only for with heat sensor)
Height: 48 mm installed in Base
Diameter: 99 mm