All Categories

DETECTORS

Explosion Proof Heat Detector

The Explosion Proof Heat Detector has Division and Zone explosion-proof ratings and is suitable for industrial and commercial applications.The detector is a signaling device to sense excessive heat or fire and send a signal to a fire alarm control panel. Its outputs include a localized LED and a fire relay. 

  • Overview
  • Related Products

The Explosion Proof Heat Detector has Division and Zone explosion-proof ratings and is suitable for industrial and commercial applications. The detector is a signaling device to sense excessive heat or fire and send a signal to a fire alarm control panel. Its outputs include a localized LED and a fire relay. 
The detector includes, a heat sensor module which is intrinsically safe, and an explosion proof integrated junction box.
The detector is suitable for explosive gas explosive atmosphere and explosive dust atmosphere.
Typical applications that use the detector include:
– Combustible storage facilities
– Munitions manufacturing
– Volatile chemical storage
– Chemical processing plants
– Petroleum refineries
– Turbine enclosures
– Battery rooms
– HVAC applications

SPECIFICATIONS
–Operating Voltage:9 to 36 Vdc (24 Vdc nominal).
–Alarm threshold: 85°C.
–Output Relay: Fire relay, Form C, 1 amperes at 30 Vdc: 
The fire relay has normally open and close in alarm. 
–Temperature Range: Operating: –40°C to +85°C. 
Storage:–40°C to +75°C.
–Humidity Range: 5 to 95% relative humidity.
–Ingress Protection: IP66 (Junction box). 
–Current: Standby current: ≤ 5mA (DC24V).
Alarm current :≤70mA (DC24V)
–Terminals: UL/CSA rated for 14-18 AWG or 2.5-0.75 mm2 wire.
 –Thread options: 1/2 inch NPT or M20. 
–Enclosure Material:Polycarbonate / ABS - Heat Detector. 
Aluminum (painted) - Junction Box
–Shipping Weight (Approximate):1.0kg.
–Dimensions: See Figure 2.
–Indicator LED: Flash in normal status , light when alarm (red)
–Magnetic Switch:Using a magnet to tough the position which has M mark on detector can simulate fire alarm,See Figure 2. 
–Latching: A detector configured for latching operation will remain in an alarm state indefinitely, after an alarm occurs.
–Latching recovery: Power outage for more than 4 seconds.
–Atex-Proof Mark: Ex db ib ⅡC  T6 Gb;
Ex ib tb ⅢC T85℃ Db.