All Categories

CALL POINT

SB106 manual call point

The conventional manual call point designed for conventional fire alarm system for reporting fire or emergency condition by its button latches. The call point has one 300 ohm resistor is used on the PCB board between Zone+ and Zone- or one relay contact (NO,COM,NC ) output when the button is pressed.

  • Overview
  • Related Products

This manual should be left with the owner/user of this equipment. 
The call points should be installed in a position where they will not be subjected to mechanical stresses,and where the temperature is within the operating temperature range. Areas where there are, or are likely to be,aggressive substances should be avoided.The conventional manual call point designed for conventional fire alarm system for reporting fire or emergency condition by its button latches. The call point has one 300 ohm resistor is used on the PCB board between Zone+ and Zone- or one relay contact (NO,COM,NC ) output when the button is pressed.

SPECIFICATIONS
※ Operating Voltage Range:9 to 28VDC Volts
※ Maximum Alarm Current (LED on): ≤50mA @ 24 VDC
※ Alarm Resistance:470ohm/1W
※ Operating Humidity Range:10% to 93% Relative Humidity,Non-condensing
※ Operating Temperature Range:-10°C to 50°C (14°F to 122°F) 
※ Dimensions: Length 86mm, Width 86mm, Depth 57mm
※ Weight: Net Weight 158g

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
Newsletter
Please Leave A Message With Us