Sequential Activator Manual

Sequential Activator Manual

The Sequential Activator functions as a result of settings on fire control Panel. The Sequential Activator operates Fixed Condensed Aerosol Generating Fire Extinguishing System Units.

  • Overview
  • Related Products

The PANEL is a 4-zone to 16-zone FACP (Fire Alarm Control Panel), which uses conventional input devices.  The panel accepts water flow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally-open contact devices. Outputs include four Notification Appliance Circuits (NAC, SOUND1-4), three standard Form-A relays (alarm, trouble and supervisory) and an EIA-485 port to interface with remote annunciators and optional remote relay modules. The FACP is field programmable via the panel keypad.  It also supervises all wiring, AC voltage and battery level. 

SPECIFICATIONS
Operating Voltage :24VDC
Releasing Input :24VDC 
Normal Standby:<30mA
Alarm: 1 A(Maximum)
Releasing Output (Class B): 24 VDC@1 A maximum load with 2.4 VDC maximum line drop
Power To Fire Single Cylinder: 900 mA
Terminals Spring leaf: 5mm pitch
Cable Capacity: 0.5 mm² to 2.5 mm² 
Wiring hole diameter: 20mm
Input Delay Time: 500 milliseconds +/-100 milliseconds
End Of Line Device: Jumper supplied
Output Duration: 2.1 seconds +/-400 milliseconds
Size: 191mmX137mmX50mm
Material: Mild Steel
Color: Light grey textured epoxy powder coated
Weight(Kg): 0.86